BRIEF INTRODUCTION
CDH-T series have output power factor 0.9. It can easily adapt to all kinds of diverse and complicated loads, such as the non-linear systems (IT systems), strongly inductive or capacitive loads, discharge lamps, and induction motors.This unit can be set up in parallel-redundant systems with up 4 units.
FEATURES & FUNCTIONS
• Online double conversion technology with DSP control
• Advanced control with Adaptive Feed Forward Cancellation (AFC) technology for very low harmonic distortion
•Output power factor 0.9
• Very low input current distortion (THDi < 1%)
• Input power factor 0.99 at 10% load
•Output efficiency up to 95%
• Space-saving compact design
• Front access makes maintenance and replacement easily
• Highly flexibility in single phase/three-phase set-ups
•Control designed to withstand all kinds of loads
• Parallel redundant operation with up to 4 units
•Variety of communication options available
• 5.7" graphic LCD panel design with multiple languates for easy-configuration
TECHNICAL DATA SHEET
MODEL | CDH10KL-T | CDH20KL-T | CDH30KL-T | CDH40KL-T | CDH60KL-T | CDH80KL-T | CDH100KL-T | CDH120KL-T |
PHASE | 3-phase in / 3-phase out | |||||||
CAPACITY | 10KVA/ 8KW | 20KVA/ 18KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | 100KVA/80KW | 120KVA/96KW |
INPUT | ||||||||
Nominal Voltage | 3x400V (3Ph + N) | |||||||
Acceptable Voltage Range | +15% or –20% | |||||||
Frequency | 50 / 60 Hz ±5 % | |||||||
Total Harmonic Distortion (THDi) | < 1.5% @ 100% load ; < 2.5% @ 50% load ; < 6.0% @ 10% load | < 1.0% @ 100% load ; < 2.0% @ 50% load ; < 5.0% @ 10% load | < 1.5% @ 100% load ; < 2.0% @ 50% load ; < 6.0% @ 10% load | |||||
Current Limitation | High overload: PFC Limit (discharging batteries) | |||||||
Power Factor | 1 | |||||||
OUTPUT/INVERTER | ||||||||
Nominal Voltage | 3x400V (3Ph + N) | |||||||
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) | |||||||
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% | |||||||
Max. Synchronisation Speed | ±10 Hz/s | |||||||
Waveform | Pure Sinewave | |||||||
Total Harmonic Distortion (THDv) | < 0.5% (Linear Load) ; < 1.5% (Non-linear Load) | |||||||
Phase Displacement | 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load) | |||||||
Dynamic Recovery Time | 10 ms. at 98 % of the static value | |||||||
Admissible Overload | Phase Overload: 125% for 10 min., 150% for 60s ; Total Overload: 112.5% for 10 min., 135% for 60s | |||||||
Admissible Crest Factor | 3.4 : 1 | 3.2 :1 | 2.8:1 | 3.2:1 | ||||
Admissible Power Factor | 0.7 inductive to 0.7 capacitive | |||||||
Imbalance Output Voltage @ 100% Unbalanced Loadt | <1% | |||||||
Current Limit | High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit | |||||||
STATIC BYPASS | ||||||||
Type | Solid state | |||||||
Voltage | 3x400V (3Ph + N) | |||||||
Frequency | 50/60 Hz | |||||||
Activation Criterion | Microprocessor control | |||||||
Transfer Time | Zero | |||||||
Admissible Overload | 400% for 10 sec. | |||||||
Transfer to Bypass | Immediate, for overloads above 150% | |||||||
Retransfer | Automatic after alarm clear | |||||||
MAINTENANCE BYPASS | ||||||||
Type | Without interruption | |||||||
Voltage | 3x400V (3Ph + N) | |||||||
Frequency | 50/60 Hz | |||||||
Overall Efficiency (Line mode) | 90.50% | 91.05% | 92% | 91.50% | 93% | 94% | 93.00% | 93.36% |
BATTERY | ||||||||
Built-in Battery Type (2x31) | 12V 7Ah | 12V 9Ah | 12V 12Ah | 12V 18AH | / | / | / | / |
Back-up Time (minutes) | 9 | 11 | 8 | 8 | / | / | / | / |
Max. Charging Current | 23.5A | 47A | ||||||
PHYSICAL | ||||||||
Dimension, DxWxH (mm) | 770x450x1100 | 705x590x1320 | ||||||
Net Weight (without batteries) (Kg) | 110 | 180 | 210 | 230 | 255 | 255 | ||
Net Weight (w/built-in batteries) (Kg) | 230 | 300 | 430 | 565 | / |