    Online UPS HF
    CDH-T
    CDH-T

    Online UPS HF 3P in/3P out

    10KVA~120KVA






     

    BRIEF INTRODUCTION

     

    CDH-T series have output power factor 0.9. It can easily adapt to all kinds of diverse and complicated loads, such as the non-linear systems (IT systems), strongly inductive or capacitive loads, discharge lamps, and induction motors.This unit can be set up in parallel-redundant systems with up 4 units.

     

    FEATURES & FUNCTIONS

     

    • Online double conversion technology with DSP control        
    • Advanced control with Adaptive Feed Forward Cancellation (AFC) technology for very low harmonic distortion 

    •Output power factor 0.9        
    • Very low input current distortion (THDi < 1%)        
    • Input power factor 0.99 at 10% load        
    •Output efficiency up to 95%        
    • Space-saving compact design        
    • Front access makes maintenance and replacement easily        
    • Highly flexibility in single phase/three-phase set-ups        
    •Control designed to withstand all kinds of loads        
    • Parallel redundant operation with up to 4 units        
    •Variety of communication options available        
    • 5.7" graphic LCD panel design with multiple languates for easy-configuration

     

     

    TECHNICAL DATA SHEET

     

    MODELCDH10KL-TCDH20KL-TCDH30KL-TCDH40KL-TCDH60KL-TCDH80KL-TCDH100KL-TCDH120KL-T
    PHASE3-phase in / 3-phase out
    CAPACITY10KVA/ 8KW20KVA/ 18KW30KVA/24KW40KVA/32KW60KVA/48KW80KVA/64KW100KVA/80KW120KVA/96KW
    INPUT
    Nominal Voltage3x400V (3Ph + N)
    Acceptable Voltage Range+15% or –20%
    Frequency50 / 60 Hz ±5 %
    Total Harmonic Distortion (THDi)< 1.5% @ 100% load ; < 2.5% @ 50% load ; < 6.0% @ 10% load< 1.0% @ 100% load ; < 2.0% @ 50% load ; < 5.0% @ 10% load< 1.5% @ 100% load ; < 2.0% @ 50% load ; < 6.0% @ 10% load
    Current LimitationHigh overload: PFC Limit (discharging batteries)
    Power Factor1
    OUTPUT/INVERTER
    Nominal Voltage3x400V (3Ph + N)
    PrecisionStationary: ±1% ; Transitory: ±2% (load variations 100-0-100%)
    Frequency50/60 Hz synchronised ±4 % With mains absent ±0.05%
    Max. Synchronisation Speed±10 Hz/s
    WaveformPure Sinewave
    Total Harmonic Distortion (THDv)< 0.5% (Linear Load) ; < 1.5% (Non-linear Load)
    Phase Displacement120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)
    Dynamic Recovery Time10 ms. at 98 % of the static value
    Admissible OverloadPhase Overload: 125% for 10 min., 150% for 60s ; Total Overload: 112.5% for 10 min., 135% for 60s
    Admissible Crest Factor3.4 : 13.2 :12.8:13.2:1
    Admissible Power Factor0.7 inductive to 0.7 capacitive
    Imbalance Output Voltage @ 100% Unbalanced Loadt<1%
    Current LimitHigh overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit
    STATIC BYPASS
    TypeSolid state
    Voltage3x400V (3Ph + N)
    Frequency50/60 Hz
    Activation CriterionMicroprocessor control
    Transfer TimeZero
    Admissible Overload400% for 10 sec.
    Transfer to BypassImmediate, for overloads above 150%
    RetransferAutomatic after alarm clear
    MAINTENANCE BYPASS
    TypeWithout interruption
    Voltage3x400V (3Ph + N)
    Frequency50/60 Hz
    Overall Efficiency (Line mode)90.50%91.05%92%91.50%93%94%93.00%93.36%
    BATTERY
    Built-in Battery Type (2x31)12V 7Ah12V 9Ah12V 12Ah12V 18AH////
    Back-up Time (minutes)91188////
    Max. Charging Current23.5A 47A
    PHYSICAL
    Dimension, DxWxH (mm)770x450x1100705x590x1320
    Net Weight (without batteries) (Kg)110180210230255255
    Net Weight (w/built-in batteries) (Kg)230300430565/